Mr. Bernard P. Orlan April 25, 2002
Indoor Air Quality Measurements Page 3
Stuyvesant High School (M477) __________ ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and twenty (120) sets of real-time environmental measurements
consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All
ten floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after
12:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 65.6°F to 74.6°F. One (1) of the
measurements was below the nmgc of 68 to 75°F (at 50 percent relative humidity) recommended
by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor
temperature range was 58.2 to 59.5°F.
RelatiyeHumidity
The relative humidity indoors ranged from 26.4 percent to 32.6 percent. Sixty-three (63)
measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant
comfort.. The outdoor relative humidity levels were 22.8 and 24.0 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 425 ppm to 1132 ppm. One (1) of the CO2
measurements was above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentrations were 424 and 426 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1126 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1
ppm.
Respirable Particulates (PM2j)
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 19 pg/m^ with an
average of approximately 12 pg/m^. None of the measurements were above the NPAAQS of 65
pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter or the USEPA recommendation of 40 pg/m^ for sensitive individuals and
children. The outdoor respirable particulate concentrations were 15 and 17 pg/m^.