SCOPE OF WORK for IAQ tests at PS 234M, June 2002.

NYC-WTC_000372173–000372176
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan June 19, 2002 Indoor Air Quality Assessment Page 4 P. S. 234M ATC Project No. 15-19125-0279

respirable particulate concent ation ranged from 41 pg/m^ to 44 pg/m^ with an average of approximately 42 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

Ti'OC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The building was occupied at the time of the assessment; • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO, and TVOCs were below applicable standards and guidelines. 2. Twenty-five (5) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. 3. All of the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. None of the measurements collected indoors for respirable particulate concentrations were above the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. 5. One (1) of the indoor CO2 measurement was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely, Reviewed by: /< TC ASSOCIA TES INC.

'iannis Efstathiou James R. Cohn, CH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CITY_21MC100_002852209

NYC-WTC_000372176

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000372176Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →