NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, PS 234M, May 15, 2002

Machine-extracted title · confidence 58%

Indoor air quality measurements collected May 15, 2002 at PS 234M.

NYC-WTC_000371987–000371990
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 10, 2()()2 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Protect No. 15-19125-0229 Real-Timf. Environmental Measvrements

A fC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one (51) from inside the school building and nine (9) outdoors. All three Poors of the school were surr'cyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded after 4:30 P.M.

Temiferature

Indoor dr, bulb temperature measurements ranged from 60 °F to 76 °F. Fifteen (15) indoor measurements for temperature were below' the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 56.2 to 61.8 °F.

Relaiive Humidity

The relative humidity indoors ranged from 25 percent to 36.7 percent. Twenty-five (25) indoor measurements for relative humidity were below the ASHRAE-recommencied range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 21 to 28.9 percent.

Carbon Dio.tide Concentration

Carbon dioxide concentrations indoors ranged from 430 ppm to 870 ppm. All of the measurements were below' the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 391 ppm. Therefore, the maximum acceptable level of CO2 at thus location was 1091 pprn (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors was 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations w'as 1 ppm for all readi:ngs.

Respirable Particulates (PM2 5)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 26 pg/m^ with an average approximately 12 pg/m^- All measurements collected indoors for respirable particulate concentrations were below' the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.:) micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m-^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 10 pg/m^ to 20 pg/m^ with an average of approximately 16 pg/m3.

CITY_21MC100_002851955

NYC-WTC_000371989

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000371989Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →