NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 10,2002
Indoor Air Quality Assessment Page 4
P. S. 234M ATC Project No. 15-19125-0279
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concisntr^ion
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0 .0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented;
1. Concentrations of CO and TVOCs were below applicable standards and guidelines.
2. Forty-four (44) indoor measurements for temperature were below the range of 73 to 79°F (at
50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the
summer season.
3. All indoor measurements for relative humidity were within the ASHRAE-recommended
range of 30 to 60 percent for occupant comfort.
4. All measurements collected indoors for respirable particulate concentrations were below the
NPAAQS 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or
less in aerodynamic diameter or the USEPA recommended concentration of 40 pg/m3 for
sensitive individuals and children.
5. One (1) CO2 measurement was above the ASHRAE Standard 62-1999 recommended
maximum concentration of <700 ppm above the background level.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or 212.
Sincerely,
TCASSOCIA TES INC.
Reviewed by:
7
James R. Cohn, CIH, CSP
Senior Pro ject Manager Regional Manager, Industrial Hygiene Division
Attachment
CITY_21MC100_0 02851923
NYC-WTC_000371956