NYC-WTC_000397369
Indoor air quality measurements collected on Apr 29, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗ATC IAQ measurements collected at P.S. 234M in April 2002.
NYC-WTC_000371895–000371898OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 30,2002 Indoor Air Quality Assessment Page 3 P. S. 234M______________________________ ATC Project No. 15-19125-0279 Real-Time Environmental Measurements
ATC collected sixty (60) sets of real-time enyironmental measurements consisting of fifty-one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded after 4:05 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 67.6°F to 76.6 °F. Nineteen (19) of the indoor measurements for temperature were below and thirty-two (32) measurements were within the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 48.6 to 52 °F.
Relative Humidity
The relative humidity indoors ranged from 27.3 percent to 38.6 percent. Seventeen (17) of the indoor measurements for relative humidity were below and thirty-four (34) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 20.2 to 21.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 520 ppm to 958 ppm. All of the measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 468 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1168 ppm (background level •+• 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm for alt readings.
Respirable Particulates (PM2,3)
Respirable particulate concentrations* indoors ranged between 3 ^g/m^ to 13 gg/m^ with an average 6 gg/m^- All measurements collected indoors and outdoors for respirable particulate concentrations were below the NPAAQS 65 gg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 gg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 3 gg/m^ to 11 gg/m^ with an average of 6 gg/m^.
CITY_21MC100_002851845
NYC-WTC_000371897
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000397369
Indoor air quality measurements collected on Apr 29, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315072
ATC IAQ measurements collected April 29, 2002 for P.S. 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315193
Indoor air quality measurements collected May 15, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315204
Indoor air quality measurements collected May 16, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397389
ATC provides IAQ measurements at P.S. 234M, as part of BOE program to maintain IAQ, May 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397479
ATC reports indoor air quality measurements at PS 234M, May 2002, per BOE request.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397475
ATC IAQ measurements at PS234M, May 15, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315208
Indoor air quality measurements collected May 17, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397561
ATC IAQ measurements collected May 31, 2002 for PS234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397321
ATC IAQ measurements collected at PS 234M per BOE request on Apr 19, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199217
ATC Associates reports indoor air quality measurements collected at P.S. 234M on May 30, 2002 for the NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397355
Indoor air quality measurements recorded April 26, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000315072
ATC IAQ measurements collected April 29, 2002 for P.S. 234M.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397369
Indoor air quality measurements collected on Apr 29, 2002 at PS 234M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397389
ATC provides IAQ measurements at P.S. 234M, as part of BOE program to maintain IAQ, May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397365
IAQ measurements collected on Apr 26-29, 2002 for PS 234M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315061
Indoor air quality measurements collected April 26, 2002 for PS 234M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315039
Air quality measurements taken April 24, 2002 for PS 234M, per BOE program.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000397369
Indoor air quality measurements collected on Apr 29, 2002 at PS 234M.
Similar indexed content
NYC-WTC_000315072
ATC IAQ measurements collected April 29, 2002 for P.S. 234M.
Similar indexed content
NYC-WTC_000315193
Indoor air quality measurements collected May 15, 2002 at PS 234M.
Similar indexed content
NYC-WTC_000315204
Indoor air quality measurements collected May 16, 2002 at PS 234M.
Similar indexed content
NYC-WTC_000397389
ATC provides IAQ measurements at P.S. 234M, as part of BOE program to maintain IAQ, May 2002.
Similar indexed content