NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, PS 234M, Apr 2002

Machine-extracted title · confidence 64%

ATC IAQ measurements collected at PS 234M in April 2002.

NYC-WTC_000371877–000371880
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 24,002 Indoor Air Quality Assessment Page 3 P. S. 234M______________________________ ATC Project No. 15-19125-0279 Real-Time Environmental. Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. Tliese results are described below.

Field data sheets are found in Attachment 1. Readings began at 2 P.M. and concluded after 4:00 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 65.7 °F to 73 °F. Fifty (50) indoor measurements for temperature were below the range and one (1) measurement was within the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55- 1992 during the summer season. The outdoor temperature measurements ranged from 46.7 to 47.4 °F.

Relative Humidity

The relative humidity indoors ranged from 23 percent to 34 percent. Thirty-two (32) indoor measurements for relative humidity were below and nineteen (19) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 28.8 to 46.8 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 485 ppm to 960 ppm. All of the measurements were below' the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 447 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1147 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration .

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 0 ppm for all readings.

Respirable Particulates (PM2^5)

Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 19 pg/m^ with an average 10 pg/m^- All measurements collected indoors and outdoors for respirable particulate concentrations were below the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 13 pg/m^ to 17 pg/m^ with an average of 15 pg/m^.

CITY_21MC100_002851801

NYC-WTC_000371879

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000371879Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →