Mr. Bernard P. Orlan April 19,002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279
Real-Time Environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 2 P.M. and concluded after 4 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 71.8 °F to 78.6 °F. Seven (7) indoor measurements for temperature were bellow the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 80.5 to 84.9 °F.
Relative Humidity
The relative humidity indoors ranged from 42.7 percent to 48 percent. All indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 43.1 to 52.5 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 608 ppm to 888 ppm. All of the measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 528 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1228 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 2 ppm to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm .The outdoor CO concentrations were 3 ppm.
Respirable Particulates (PM2^)
Respirable particulate concentrations* indoors ranged between 18 pg/m^ to 38 pg/m^ with an average 31 pg/m^- All measurements collected indoors for Respirable particulate concentrations are within the limits of NPAAQS 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 30 pg/m^ to 50 pg/m^ with an average of 37 pg/m^.
CITY_21MC100_002851768
NYC-WTC_000371859
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000397311
Indoor air quality measurements conducted at PS 234M; BOE program participation.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397335
ATC IAQ measurements collected on Apr 24, 2002 for PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397331
Indoor air quality measurements collected April 22, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314999
ATC indoor air quality measurements conducted April 18, 2002, for P.S. 234M per BOE request.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315017
Indoor air quality measurements for PS 234M, date April 22, 2002, per BOE request.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372119
ATC IAQ measurements at PS 234M for BOE, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397321
ATC IAQ measurements collected at PS 234M per BOE request on Apr 19, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315134
ATC IAQ measurements at PS 234M for BOE program, May 7, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315372
ATC IAQ measurements report for P.S. 234M prepared for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397345
BOE-required IAQ measurements at PS 234M; report date April 25, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199202
Letter from ATC Associates reporting indoor air quality measurements collected at P.S. 234M on April 19, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397429
ATC IAQ measurements at PS234M for DOE program, May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000397311
Indoor air quality measurements conducted at PS 234M; BOE program participation.
Similar indexed content
NYC-WTC_000397335
ATC IAQ measurements collected on Apr 24, 2002 for PS 234M.
Similar indexed content
NYC-WTC_000397331
Indoor air quality measurements collected April 22, 2002 at PS 234M.
Similar indexed content
NYC-WTC_000314999
ATC indoor air quality measurements conducted April 18, 2002, for P.S. 234M per BOE request.
Similar indexed content
NYC-WTC_000315017
Indoor air quality measurements for PS 234M, date April 22, 2002, per BOE request.
Similar indexed content