NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ measurements report, High School for Leadership, Mar 2002

Machine-extracted title · confidence 55%

ATC IAQ measurements conducted March 4, 2002 at the referenced NYC BOE school.

NYC-WTC_000370407–000370410
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 5, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service ('M894') ATC Project No. 15-19125-0290

TVOC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at . the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of respirable particles, CO2, CO and TVOCs were below applicable standards and guidelines. 2. One hundred and twenty-five (125) indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Three (3) indoor measurements were within the ASHRAE recommended range. 3. Seven (7) indoor measurements for temperature were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 336 or 212.

Sincerely, Reviewed by: A TC ASSOCIA TES INC.

James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_002865636

NYC-WTC_000370410

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000370410Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000370422

Indoor air quality measurements collected March 6, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000370411

ATC IAQ measurements conducted March 5, 2002 at the referenced NYC BOE school.

Similar indexed content

NYC-WTC_000259914

IAQ field report with conditions and scope of work, Mar 6, 2002

Similar indexed content

Compare copies and versions →