Mr. Bernard P. Orlan May 23, 2002
Indoor Air Quality Assessment Page 3
P. S. 89M_______________________________ ATC Project No. 15-19125-0297
» Real-Time Environmental Measurements
ATC collected seventy-nine (80) sets of realTime environmental measurements consisting of
seventy-one (71) from inside the school building and nine (9) from outdoors. All five floors of
the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at
approximately 11:30 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 67.5°F to 74 °F. Fifty-eight (58) of the
indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative
humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season . The
outdoor temperature measurements ranged from 59.6 °F to 60.3 °F.
Relative Humidity
The relative humidity indoors ranged from 26.3 to 32.3 percent. Sixty-two (62) of the indoor
measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60
percent for occupant comfort. The outdoor relative humidity measurements ranged from 33.1 to
34.0 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 544 ppm to 1199 ppm. All of the indoor
measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 568 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1268 ppm (background level + 700 ppm). Carbon dioxide measurements are used
as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant
respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2
ppm for all collected readings.
Respirable Particulates (PM2
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 20 pg/m^. The
average PM2.5 concentration for the entire school building was approximately 11 pg/m^. All of
the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration
of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor
respirable particulate concentration measurements ranged from 23 to 26 pg/m^ with an average
of 24 pg/m^.