NYC 9/11 Public Portal Document
HftX NU. Eiki fB« lb4U r ua
ULU-U4-LT tut Ue:H HHBltNl bKUUa INU
AMBIENT GROUP, INC.
10 MORRIS AVENUE
GLEN COVE, NY 11542
ELAP# 10865
METALS IN AIR LABORATORY DATA REPORT
PROJECT ID; 211338 COLLECTED; 11/27/01
CLIENT; CUSHMAN & WAKEFIELD, INC. DATEREC'D: 11/29/01
PROJECT ADDRESS; ONE NORTH END AVENUE ANALYZED; 11/29/01
DESCRIPTION; 3RD FLOOR: ADJ. TO STAIR D
LABORATORY ID FIELD ID ANALYTE VOLUME (L) ug/m’
40773 6403-2 CADMIUM 640 0.7S
CHROMIUM 640 7.03
COPPER 640 4.30
IRON 640 4.30
LEAD 640 6.64
manganese 640 1.17
NICKEL 640 1.95
ZINC 640 7.03
Stindirti/Guidenne:
OSHA PEL far Cadmhinf. Sug/tn3; OSHA PEL for Chromium- 1000ug/rn3; OSHA PEL for Capper- 1oocug/m3: OSHA PEL far
Iron: 10DO0ug/fn3; OSHA PEL far Lead-. 50ug/in3'. OSHA PEL far Manganesor 1OO0ugZm3; OSHA PEL far Nickel: 100pug/m3;
OSHA PEL for Zinc; 5a00ug/m2