06/T0/m2_10;^ FA^212_353_8326 __ __ ATC igioos

Mi. Bernard P. Orlan June 10, 2002 Indoor Air Quality Assessment Paged P. S, 150M______________ _ ATCPrpicctNpa549125s0289 respirable particulate concentration measurements ranged from 8 to 18 ug/m^ with an average of 14p,g/m3. * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concsntrations

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • There was construction work going on in the plaza; • The school building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FUNDINGS

Based on the real-time measurements, the follcrwing findings are presented:

1. Concentrations of indoor respirable particulates, CO, and TVOCs were within applicable standards and guidelines. 2. Twelve (12) of the indoor measurements were bellow the range of 73 to 79"F (at 50 percent relative humidity) as recommended by tire ASHRAE Standard 55-1992 during the mechanical cooling season (summertirne conditions). 3. All of the indoor relative humidity measurements were within the ASHRAE-reconuncnded range of 30 to 60 percent for occupant comfort. 4. The highest CO? measurement was recorded in room # 504 (1262 ppm) with 24 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-3280, extension 211 or 290.

Sincerely, Reviewed by; ATCASSOCLATHS INC.

Prasad Doddapeneni James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CITY_21MC1OO_OO9253271 NYC-WTC_000359997

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000359997Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →