ATC I21004 01/28/2002 09:14 FAX 212 353 8306

Mr. Bernard P, Orlan January 28, 2002 Ind.oor Air Quality Assessment Page 3 P- S- 89M ATCProiectNcLl5-19125rQ297

real-Time Environmental measdreivtents

ATC collected eighty (80) sets of real-time environmental measuremenis consisting of seventy- two (72) from inside the school building and eight (8) outdoors. All five floors of the school were surveyed. These results arc described below.

Field data sheets arc found in Attachment 1. Readings began at 8:00 A-M. and concluded after 2:40 P.M,

Temperature

Indoor dry bulb temperature raeasurements ranged from 68.0 ’F to 73.9 ’F. All measurements were within the range of 68 to 75“F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the beating season (wintertime conditions). The outdoor temperature measurements ranged from 44.8 to 50.9”?.

Relalrve //umidity

The relative humidity indoors ranged from 16.8 percent to 29.2 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 19.0 to 31.2 percent.

Carbon Dioxide Conceniratipn

Carbon dioxide concentrations indoors ranged from 4S8 ppm to 1690 ppm. Two (2) COo measurement was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations ranged from 448 to 466 ppm. Therefore, tlie maximum acceptable level of CO2 at tliis location was 1166 ppm (background level 700 ppm). The highest CO2 reading was found in room 408. At the time of ATC’s assessment, this room was occupied by approximately twenty-eight (28) people. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. Tlie primary source of CO2 indoors is occupant respiration. The school building during ATC’s assessment was not occupied.

Cwban Monoxide Cancentration

Carbon monoxide concentrations indoors were Oppni for all readings- These concentrations were below the NPAAQS/A5HRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.

Respirable Particulates ('PM2.5)

Respirable particulate concentiations* indoors ranged between 6 pg/m^ to 28 pg/m^. All raeasurements were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PMo.s concentration tor the entire school building was approximately 13 pg/mA This average concentration was well below the USEPA recommended concentration of 40 pg/mJ for sensitive

CITY_21MC100_009253034

NYC-WTC_000359674

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000359674Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →