Preliminary indoor air monitoring results for 225 Broadway floor near WTC site.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗DOHMH memo detailing October 2001 air monitoring results for indoor contaminants.
NYC-WTC_000354092–000354096OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Of interest, no levels of irritant substances were detected. In general, irritant contaminants/ substances/agents which are relatively insoluble in water (H2O), such as phosgene, ozone, and oxides of nitrogen (NOx) exert effect on the lower respiratory tract. Essentially, the less soluble the substance is in ITO. the deeper and more delayed its irritant effect. Substances that are highly soluble in H2O, such as ammonia and sulfur dioxide, exert effect on the upper respiratory tract. The extent to which the irritant substances may cause adverse health effects depends on the concentrations, duration of exposure, toxicity, and solubility in H2O.
Carbon Monoxide Levels
Of interest, no CO levels were detected within the space despite continuous combustion of materials in the surrounding areas of the World Trade Center. CO is produced by incomplete combustion. The PEL 8hr (TWA) is 35 ppm, ceiling exposure limit (C) is 200 ppm, and the immediately dangerous to life and health limit (IDLH) is 1200 ppm. Based on this finding, neither personal air monitoring with respect to carbon monoxide, methylene chloride nor biological monitoring with respect to metabolites such as CoHb are warranted. A background level of CO is approximately 0.19 ppm.
Carbon Dioxide & Oxygen Levels
CO2 levels within the range of 300 ppm and 350 ppm were detected. These levels were well below the PEL of 5000 ppm. Background level of CO2 is approximately 350 ppm.
The O2 level was 21% (normal). The level suggests that the air was neither deficient nor enriched. For breathing purposes, air should not contain less than 19.4% oxygen or not exceed 23.5 % oxygen.
Thermal Comfort
Temp and RH ranged from 73.7 to 75.7 and 30% - 31 % respectively. Temp and RH were maintained within recommended guidelines. RH below 20% is associated with mucous membrane irritation.
Ventilation
Air velocity measurements at the ceiling supply diffusers ranged from 18 fpm to 310 fpm. With the exception of the air handling (AHU) which serves Classroom #1, the measurements indicated that the mechanical system that serves the space was turn off. Smoke tests at the ceiling diffusers further confirmed this finding. This finding is not unusual since in cases where ambient exposure to air contaminants are suspected, the ventilation mechanical system is usually turned off as a precautionary measure to avoid a pathway for cross-contamination, distribution, and re-distribution of possible contaminated air. Such mechanical systems are designed to provide at least 20% “fresh” outdoor air and 80% re-circulated air.
CITY_21MC100_006717302
NYC-WTC_000354094
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000279307
Preliminary indoor air monitoring results for 225 Broadway floor near WTC site.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000321987
DOH/DMH air monitoring on 23rd floor of 225 Broadway; detailed results and table in report.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000354112
DOHMH preliminary summary of IAQ measurements on 22nd floor at 225 Broadway.
12 shared non-person entities · 1 shared topics · similarity 0.966
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000319809
Document describing MS/PS 85M occupancy and recovery operations related to WTC.
9 shared non-person entities · 1 shared topics · similarity 0.946
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000276455
EPA/NCEA draft on exposure and [name] evaluation relating to World Trade Center.
10 shared non-person entities · 1 shared topics · similarity 0.941
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000318088
ASB testing results from ATC and follow-up sampling around PS 234 school building.
10 shared non-person entities · 1 shared topics · similarity 0.941
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199886
Summary of initial and follow-up asbestos testing at PS 234 school, reporting dust and air sample results regarding fiber detection.
10 shared non-person entities · 1 shared topics · similarity 0.941
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000455806
Safety and health survey of a DOE office space and HVAC system following employee complaints at 52 Chambers Street.
3 shared non-person entities · similarity 0.954
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000106330
Letter reporting asbestos testing results for air and dust at Borough of Manhattan Community College in February 2002.
8 shared non-person entities · 1 shared topics · similarity 0.949
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000220400
Report covering an indoor air quality investigation conducted at 44 Wall Street on November 13, 2001.
6 shared non-person entities · 1 shared topics · similarity 0.943
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000243565
EIA report for Law Department project at 100 Church Street by TRC.
7 shared non-person entities · 1 shared topics · similarity 0.941
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000243668
Environmental assessment prepared for NYC Law Department by TRC Engineers, April 8, 2002.
7 shared non-person entities · 1 shared topics · similarity 0.941
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000321987
DOH/DMH air monitoring on 23rd floor of 225 Broadway; detailed results and table in report.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000279307
Preliminary indoor air monitoring results for 225 Broadway floor near WTC site.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000321987
DOH/DMH air monitoring on 23rd floor of 225 Broadway; detailed results and table in report.
Similarity score 0.964 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000279307
Preliminary indoor air monitoring results for 225 Broadway floor near WTC site.
Similarity score 0.962 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000132654
A letter from Capital Properties enclosing air quality monitoring reports and cleanup summaries for buildings on Broadway and Trinity Place.
Similarity score 0.954 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000105620
Cover letter submitting additional air quality monitoring results for 111 Broadway and requesting FOIL exemption.
Similarity score 0.954 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Preliminary indoor air monitoring results for 225 Broadway floor near WTC site.
Similar indexed content
NYC-WTC_000321987
DOH/DMH air monitoring on 23rd floor of 225 Broadway; detailed results and table in report.
Similar indexed content
DOHMH preliminary summary of IAQ measurements on 22nd floor at 225 Broadway.
Similar indexed content
NYC-WTC_000455806
Safety and health survey of a DOE office space and HVAC system following employee complaints at 52 Chambers Street.
Similar indexed content
NYC-WTC_000106330
Letter reporting asbestos testing results for air and dust at Borough of Manhattan Community College in February 2002.
Similar indexed content