Stuyvesant HS/IS 306X sampling report, June 2002

Machine-extracted title · confidence 50%

Environmental sampling report for Stuyvesant HS and IS 306X conducted April 2002.

NYC-WTC_000338659–000338662
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

104 East 25th St New York, New York 1001O www.atc-enviro.com 212.353.8230 Fax 212.353.8306 ASSOCIATES INC.

Mr. Bernard P. Orlan June 6, 2002 Page 3 ;

Sample results were compared to the New York State Department of Environmental Conservation (NYSDEC) established guidelines of 0.6 parts per billion (0.6 ppb) for allowable dioxin levels in soil as per NYSDEC Memorandum HWR-94-4046, dated January 24, 1994.

Samples were collected in areas recommended by the Parents Association consultant Mr. H.A. Bader, who was present during the sampling procedures. The analytical results for the samples collected are as follows:

1- UNIT VENTILATORS

A total of ten (10) bulk samples were collected from settled dust within selected unit ventilators on the north and south sides of the building. Dioxin concentrations ranged from 0.000037 ppb to 0.003100 ppb. The concentration of dioxins in all samples collected from settled dust located within the unit ventilators are below the NYSDEC guideline of 0.6 ppb for allowable concentrations of dioxins in soil.

2. HVAC UNITS

A totaTof fourteen (14) bulk samples were collected from settled dust within the HVAC system in various locations. Dioxin concentrations ' ranged from 0.0000046 ppb to 0.000160 ppb. The concentration of dioxins in all samples collected from settled dust located within the HVAC units are all below the NYSDEC guideline of 0.6 ppb for allowable concentrations of dioxins on soil.

Exact sample locations and analytical laboratory results for the dioxin bulk samples collected is included in Appendix B of this report.

D. ASBESTOS BULK SAMPLING -UNIT VENTILATORS

1. STUYVTISANTHIGHSCHOOL

A total of ten (10) asbestos bulk samples were collected from settled dust within Unit Ventilators on the north and south sides of the building. All samples were analyzed utilizing Polarized Light Microscopy (PLM) methodology. No asbestos was detected in any of the bulk samples collected in these locations.

CITY_21MC100_008987314 NYC-WTC_000338661

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000338661Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →