Mr. Bernard P. Orlan April 24, 2002 Indoor Air Quality Measurements Page 2 Stuyvesant High School (M477') ATC Project No. 15-19125-0246 The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASWAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED PAILAMETER targetlevel AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPA.AQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer; 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASIIRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC1OO_OO3O61186 NYC-WTC_000336264
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000406753
May 16, 2002 indoor air quality measurements at Stuyvesant High School, for NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406822
Report of IAQ measurements collected May 21, 2002 at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229474
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 23, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406844
May 23, 2002 IAQ measurements at Stuyvesant High School for NYC Department of Education.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335940
Indoor air quality measurements report for Stuyvesant HS, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336107
May 2002 IAQ measurements at Stuyvesant High School for BOE.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335929
Indoor air quality measurements report for Stuyvesant HS, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335957
Indoor air quality measurements collected at Stuyvesant HS, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406861
May 28, 2002 IAQ report for Stuyvesant High School under ATC project 15-19125-0246.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336141
May 22, 2002 IAQ measurements at Stuyvesant High School for BOE.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406942
Indoor air quality field data for Stuyvesant High School, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406970
Indoor air quality measurements at Stuyvesant High School prepared for Board of Education, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000406666
Indoor air quality measurements at Stuyvesant High School, May 2002, for DOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406980
Indoor air quality measurements at Stuyvesant High School, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336098
May 13–14, 2002 IAQ measurements at Stuyvesant High School for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406953
ATC IAQ report for Stuyvesant High School to NYC Board of Education, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335912
Indoor air quality report for Stuyvesant High School, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000395300
ATC letter reporting indoor air quality assessment at Stuyvesant High School, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000406753
May 16, 2002 indoor air quality measurements at Stuyvesant High School, for NYC Board of Education.
Similar indexed content
NYC-WTC_000406822
Report of IAQ measurements collected May 21, 2002 at Stuyvesant High School.
Similar indexed content
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 23, 2002.
Similar indexed content
NYC-WTC_000406844
May 23, 2002 IAQ measurements at Stuyvesant High School for NYC Department of Education.
Similar indexed content
Indoor air quality measurements report for Stuyvesant HS, June 2002.
Similar indexed content