NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 17, 2002
Indoor Air Quality Measurements Page 4
Stuyvesant High School (M477) ATC Project No. 15-19125-0246
In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency
Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The I’M2 5
concentration range for these rooms was 12-21 pg/m^ with an average of approximately 17
Pgm-".
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs inside the building wereO.O ppm for all readings. The outdoor TVOC concentrations
were also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of interior respirable particulates, CO , and TVOCs, were below applicable
standards and guidelines.
2. All measurements of relative humidity were within the ASHRAE recommended range of 30
to 60 percent for occupant comfort.
3. Sixty-six (66) temperature measurements were above the range of 68 to 75°F (at 50 percent
relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season
(wintertime conditions).
4. One (1) CO2 measurement was above the range recommended by ASHRAE 62-1999.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or212.