Mr. Bernard P. Orlan May 29 2002 Indoor Air Quality Measurements Page 4 Stuyvesant Hieh School (M477I ATC ProiectNo. 15-19125-0246
In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 19-25 pg/m^ with an average of approximately 22 Pg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TVOC Concentration
TVOCs inside the building were 0.0 ppm for all readings. The outdoor TVOC concentrations were also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The barge operations tn pier 25 has been shut down.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of indoor respirable particulates, CO , and TVOCs were below applicable standards and guidelines. 2. Ninety-nine (99) of the indoor measurements were below and nineteen (19) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). 3. Sixty-two (62) of the indoor measurements for relative humidity were above and none of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. Eight (8) of the CO2 indoor measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading (1196 ppm) was taken in room 1004 at 2:35 PM with 30 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
CITY_21MC1OO_OO3O6O93O NYC-WTC_000336156
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000406878
May 29, 2002 IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336164
Indoor air quality measurements at Stuyvesant High School with focus on May 30, 2002 report.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336148
May 2002 IAQ measurements at Stuyvesant High School for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406604
April 23, 2002 memo describing IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406861
May 28, 2002 IAQ report for Stuyvesant High School under ATC project 15-19125-0246.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372774
IAQ measurements collected at Stuyvesant High School on April 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373022
ATC IAQ report for Stuyvesant High School dated May 31, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406844
May 23, 2002 IAQ measurements at Stuyvesant High School for NYC Department of Education.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373161
Indoor air quality measurements collected at Stuyvesant High School, June 12, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406937
Indoor air quality measurements collected at Stuyvesant High School in June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406753
May 16, 2002 indoor air quality measurements at Stuyvesant High School, for NYC Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406883
May 30, 2002 IAQ measurements at Stuyvesant High School for Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000406878
May 29, 2002 IAQ measurements at Stuyvesant High School.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336164
Indoor air quality measurements at Stuyvesant High School with focus on May 30, 2002 report.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336148
May 2002 IAQ measurements at Stuyvesant High School for BOE.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406861
May 28, 2002 IAQ report for Stuyvesant High School under ATC project 15-19125-0246.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406937
Indoor air quality measurements collected at Stuyvesant High School in June 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000213095
Cover letter and report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on May 28, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000406878
May 29, 2002 IAQ measurements at Stuyvesant High School.
Similar indexed content
NYC-WTC_000336164
Indoor air quality measurements at Stuyvesant High School with focus on May 30, 2002 report.
Similar indexed content
May 2002 IAQ measurements at Stuyvesant High School for BOE.
Similar indexed content
NYC-WTC_000406604
April 23, 2002 memo describing IAQ measurements at Stuyvesant High School.
Similar indexed content
NYC-WTC_000406861
May 28, 2002 IAQ report for Stuyvesant High School under ATC project 15-19125-0246.
Similar indexed content