Mr. Bernard P. Orlan May 29 2002 Indoor Air Quality Measurements Page 4 Stuyvesant Hieh School (M477I ATC ProiectNo. 15-19125-0246

In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 19-25 pg/m^ with an average of approximately 22 Pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs inside the building were 0.0 ppm for all readings. The outdoor TVOC concentrations were also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The barge operations tn pier 25 has been shut down.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of indoor respirable particulates, CO , and TVOCs were below applicable standards and guidelines. 2. Ninety-nine (99) of the indoor measurements were below and nineteen (19) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). 3. Sixty-two (62) of the indoor measurements for relative humidity were above and none of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. Eight (8) of the CO2 indoor measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading (1196 ppm) was taken in room 1004 at 2:35 PM with 30 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

CITY_21MC1OO_OO3O6O93O NYC-WTC_000336156

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000336156Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000336148

May 2002 IAQ measurements at Stuyvesant High School for BOE.

Similar indexed content

Compare copies and versions →