May 16, 2002 indoor air quality measurements at Stuyvesant High School, for NYC Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗IAQ measurements conducted May 21, 2002 at Stuyvesant High School.
NYC-WTC_000336136–000336140OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 22, 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477)_______________ AICProiectNpM5-19125-(^ Real-Time En \1 ronmental Measl rem eyes
ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 12:35 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 67..2°F to 73.4°F. One hundred and sixteen(116) of the indoor measurements were below (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). The outdoor temperature range was 56.1 to 63.8°F.
Relative Humidity
The relative humidity indoors ranged from 29.6 percent to 36.1 percent. Six (6) of the measurements were below' the ASHRAE-recommended range of 30 to 60 percent for occupant comfort.. The outdoor relative humidity levels were 31.8 and 33.4 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 468 ppm to 1181 ppm. Thirteen (13) of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 394 ppm and 402 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1102 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 0 ppm for both readings.
Respirable Particulates (PM2,3)
Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 17 pg/m^ with an average of approximately 11 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 15 and 18 pg/m3.
Cl'TY_21MC100_003 06 0853
NYC-WTC_000336138
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000406753
May 16, 2002 indoor air quality measurements at Stuyvesant High School, for NYC Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406822
Report of IAQ measurements collected May 21, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406844
May 23, 2002 IAQ measurements at Stuyvesant High School for NYC Department of Education.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406942
Indoor air quality field data for Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336107
May 2002 IAQ measurements at Stuyvesant High School for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372955
ATC IAQ report for Stuyvesant High School (M477) dated May 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335940
Indoor air quality measurements report for Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336263
ATC reports IAQ measurements collected at Stuyvesant High School on Apr 23, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335957
Indoor air quality measurements collected at Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274066
Report of IAQ measurements at Stuyvesant High School, May 31, 2002, for NYC Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406788
Indoor air quality measurements at Stuyvesant High School conducted May 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335929
Indoor air quality measurements report for Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000373143
ATC indoor air quality report covering measurements at Stuyvesant High School, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373161
Indoor air quality measurements collected at Stuyvesant High School, June 12, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336034
IAQ measurements collected June 26, 2002; BOE requested Stuyvesant HS results.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406980
Indoor air quality measurements at Stuyvesant High School, June 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336153
May 28, 2002 IAQ measurements at Stuyvesant High School.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406733
IAQ measurements at Stuyvesant High School, May 2002, for DOE.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000406753
May 16, 2002 indoor air quality measurements at Stuyvesant High School, for NYC Board of Education.
Similar indexed content
NYC-WTC_000406822
Report of IAQ measurements collected May 21, 2002 at Stuyvesant High School.
Similar indexed content
NYC-WTC_000406844
May 23, 2002 IAQ measurements at Stuyvesant High School for NYC Department of Education.
Similar indexed content
NYC-WTC_000406942
Indoor air quality field data for Stuyvesant High School, June 2002.
Similar indexed content
May 2002 IAQ measurements at Stuyvesant High School for BOE.
Similar indexed content