NYC-WTC_000406753
May 16, 2002 indoor air quality measurements at Stuyvesant High School, for NYC Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗IAQ measurements conducted May 21, 2002 at Stuyvesant High School.
NYC-WTC_000336136–000336140OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
104 East 25th St., 10th Floor New York, New York 10010 www.atc-enviro.com 212.353.8280 Fax 212.353.8306 ASSOCIATES INC.
May 22, 2002
Mr. Bernard P. Orlan Director, Environmental Health & SafeN New York City Board of Education 28-11 Queens Plaza North Long Island City, NY 11101 -4008
Re: Indoor Air Quality Assessment Stuyvesant High School (M477) 345 Chambers Street .New York, New York 10007 ATC Project No. 15-19125-0246
Dear Mr. Orlan;
ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on May 21, 2002, at the referenced school. The New York City Board of Education (BOE) requested these measurements as part of a program to determine if acceptable indoor air quality is being maintained.
SCOPE OF WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity, carbon dioxide (COj) and carbon monoxide (CO).
Total volatile organic compounds (TVOCs) and respirable particulates were also measured.
Herant Antonyan, Environmental Technician, of ATC’s New York City office, conducted the assessment. ATC’s findings and conclusions are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.
ATC measured temperature, relative humidity, CO, and CO with a Q-Trak® Model 8551, manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates (PM2.5) with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy.
CITY_21MC100_003060851
NYC-WTC_000336136
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000406753
May 16, 2002 indoor air quality measurements at Stuyvesant High School, for NYC Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406822
Report of IAQ measurements collected May 21, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406844
May 23, 2002 IAQ measurements at Stuyvesant High School for NYC Department of Education.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406942
Indoor air quality field data for Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336107
May 2002 IAQ measurements at Stuyvesant High School for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372955
ATC IAQ report for Stuyvesant High School (M477) dated May 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335940
Indoor air quality measurements report for Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336263
ATC reports IAQ measurements collected at Stuyvesant High School on Apr 23, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335957
Indoor air quality measurements collected at Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274066
Report of IAQ measurements at Stuyvesant High School, May 31, 2002, for NYC Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406788
Indoor air quality measurements at Stuyvesant High School conducted May 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335929
Indoor air quality measurements report for Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000336294
ATC IAQ measurements collected at Stuyvesant High School on Apr 29, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336102
Indoor air quality measurements conducted May 14, 2002 at Stuyvesant High School.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335962
Station measurements at Stuyvesant High School IAQ requested by NYC BOE, June 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406753
May 16, 2002 indoor air quality measurements at Stuyvesant High School, for NYC Board of Education.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406576
April 16, 2002 memo documenting IAQ measurements at Stuyvesant High School.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336056
IAQ measurements collected May 1, 2002 for Stuyvesant High School; BOE request.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000406753
May 16, 2002 indoor air quality measurements at Stuyvesant High School, for NYC Board of Education.
Similar indexed content
NYC-WTC_000406822
Report of IAQ measurements collected May 21, 2002 at Stuyvesant High School.
Similar indexed content
NYC-WTC_000406844
May 23, 2002 IAQ measurements at Stuyvesant High School for NYC Department of Education.
Similar indexed content
NYC-WTC_000406942
Indoor air quality field data for Stuyvesant High School, June 2002.
Similar indexed content
May 2002 IAQ measurements at Stuyvesant High School for BOE.
Similar indexed content