Indoor air quality report, Stuyvesant HS, May 2002

Machine-extracted title · confidence 33%

IAQ measurements collected May 6, 2002; Stuyvesant High School, BOE.

NYC-WTC_000336069–000336072
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 7, 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477)_________ . ATC Project No. 15-19125-0246 Real-Time E\’\iRo>’MEMAi..MEAStREMENTS

ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 12:25 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 68.6°F to 72.4°F. All of the measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (summertime conditions). The outdoor temperature range was 60.1 to 67.2°F.

Relative f/umidity

The relative humidity indoors ranged from 47.1 percent to 56.8 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort.. The outdoor relative humidity levels were 51.6 and 52.5 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 453 ppm to 1194 ppm. Twelve (12) of the COg measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 430 ppm and 448 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1148 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

CqrbonMonpxide Concentratim

Carbon monoxide concentrations indoors ranged from 0 pprn to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor GO concentrations were 1 ppm.

Respirable Particulates (PM2,^)

Respirable particulate concentrations* indoors ranged between 30 pg/m^ to 52 pg/m^ with an average of approximately 41 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Seventy-seven (77) indoor measurements were above the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 72 and 81 pg/m^.

CITY_21MC100_003060651 NYC-WTC_000336071

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000336071Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →