NYC 9/11 Public Portal Document

, Mr. Bernard P. Orlan February 7, 2002 Indoor .Air Quality Assessment Page 3 H.S. for Leadership & Pub. Service fMSPA) ATC Project No. 15-19125-0290

Rea l-Time E.nmronmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and thirty-four (134) in the school building and six (6) outdoors. .411 fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8:00 A.M. and concluded after 3:10 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 64.2°F to 74.2°F. Thirteen (13) of the measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor tempera.ture range was 43.3°F to 46.6°F.

Relative Humiditv

The relative humidity indoors ranged from 19.4 percent to 31.1 percent. Only (1) measurement was within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All ' other relative humidity measurements were below the recommended range. The outdoor relative humidity range was 21.4 and 23.8 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 452 ppm to 1374 ppm. Three (3) of the measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentrations ranged from 423 ppm to 462 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1162 ppm (background level -1- 700 ppm). The highest reading was recorded in Room B-06, occupied by 37 people at around 10:30 A.M. The CO2 level in room B- 06 at around 3:00 P.,M. was only 847 ppm. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COg indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 2-3 ppm.

Respirable Particulates (PM2j)

Respirable particulate concentrations* indoors ranged between 6 pig/m^ to 27 pg/m^. None of the measurements v/ere above the NPAAQS of 65 ug/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations ranged from 54 pg/m^ to 73 pg/m^ with an a\'erage of 65 pg/ra^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC100_006752157

NYC-WTC_000335347

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000335347Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000335364

ATC IAQ measurements collected February 8, 2002 for the referenced school.

Similar indexed content

Compare copies and versions →