NYC-WTC_000399500
ATC IAQ measurement letters sent to BOE regarding 90 Trinity Place, late May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Indoor air quality measurements at M894; June 18, 2002.
NYC-WTC_000335281–000335284OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan June 18, 2002 Indoor Air Quality Assessment Page 3 H.S . for Leadership & Public Service (M894) ATC Project No. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.
Temperature
Indoor dry' bulb temperature measurements ranged from 72.2 to 81.3 °F. Five (5) of the indoor measurements for temperature were below and four (4) of the measurements were above the range of 73 to79 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55- 1992 during the summer season. The outdoor temperature ranged from 76.8 to 83.1 °F.
Relative Humidity
The relative humidity indoors ranged from 41.6 percent to 48.9 percent. All of the indoor measurements for relative humidity' were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 39.4 to 45.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 570 ppm to 1126 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 682 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1382 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the 1'>1P?lAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.
Respirable Particulates (PM2 3)
Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 18 pg/m^ with an average 8 pg/m-’- None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 42 pg/m- to 83 pg/m^ wiih an average of 60 pg/m^.
CITY_21MC100_003058672
NYC-WTC_000335283
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000399500
ATC IAQ measurement letters sent to BOE regarding 90 Trinity Place, late May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399528
June 10, 2002 IAQ measurements update letter to BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335285
Indoor air quality measurements at M894; June 19, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292004
ATC IAQ measurements collected June 17, 2002 for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291984
ATC IAQ measurements collected June 10, 2002 for the school per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291988
ATC IAQ measurements collected June 11, 2002 for the referenced BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399496
Indoor air quality report for the referenced NYC BOE school, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399272
May 2002 IAQ measurements at High School for Leadership & Space; BOE requested assessment.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000188377
Memo reporting indoor air quality measurements collected at a school on May 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291976
ATC IAQ measurements conducted June 4, 2002 for BOE at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335293
Indoor air quality measurements at M894; June 21, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000188385
Memo reporting indoor air quality measurements collected at a school on June 7, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000292004
ATC IAQ measurements collected June 17, 2002 for the referenced school.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399524
June 7, 2002 IAQ measurements update letter to BOE for the school.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410915
IAQ measurements at 90 Trinity Place; BOE requested assessment of air quality.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410939
Documentation of accreditation scope for bulk asbestos analysis at ATC lab.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399528
June 10, 2002 IAQ measurements update letter to BOE.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291984
ATC IAQ measurements collected June 10, 2002 for the school per BOE request.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000399500
ATC IAQ measurement letters sent to BOE regarding 90 Trinity Place, late May 2002.
Similar indexed content
NYC-WTC_000399528
June 10, 2002 IAQ measurements update letter to BOE.
Similar indexed content
NYC-WTC_000335285
Indoor air quality measurements at M894; June 19, 2002.
Similar indexed content
ATC IAQ measurements collected June 17, 2002 for the referenced school.
Similar indexed content
ATC IAQ measurements collected June 10, 2002 for the school per BOE request.
Similar indexed content