NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan October 14, 2002
Respirable Particulate Sampling Page 2
P.S. 150M ATC Project No. 15-19125-0289
Table 1 lists target guideline for the parameter that ATC evaluated during this
investigation. Meeting the listed value does not assure that Acceptable indoor air quality
will be achieved at all times. 7
i; : -7 T^^ )
TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETER
EVALUATED
TXRGET LEVEL
_____________ __________ __
i|
Respirable. 65 micrograms per cubic USEPA NPAAQS jl
Particulates (PMj 5) meter of air (pg/m^) 24-hdur
average-
Respirable 40 pg/m ■ 24-hour average USEPA - Recommendation for
Particulates (PMss) children/sensitive individuals ’
USEPA = United States Eiiviromnehtal Protection Agency '
NPAAQS = National Primary Ambient-Air Quality Standard
RESULT
ATC collected one (1) 24-hour PM, 5 sample in the schooPs Main Lobby.
The 24-hour average concentration of PMj 5 was 11.8 ug/m^ which is below both the EPA
NPAAQS for PM2.5 of 65 ug/m’ and the EPA recommended level of 40 ug/m\ ii
Ji
It is our pleasure to provide these indoor air consultative services to the New York City
Department of Education. If you have any questions about this report, please call (212)
253-8280,Extension 212. • i 4,
t
Sincerely,)
ATG ASSOCIATES INC.
James R. Cohn, CIH, CSP
’ Regional Manager
Industrial Hygiene Division