NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, PS 89M, Warren St, Apr 2002

Machine-extracted title · confidence 40%

Indoor air quality measurements collected on multiple dates for PS 89M.

NYC-WTC_000328280–000328283
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 17, 2002 Indoor Air Quality Assessment Page 4 P. S. 89M _________________________ ATC Project No. 15-19125-0297 measurements ranged from 84 to 109 pg/m^ with an average of 96 pg/m^. All of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All of the ten (10) instantaneous outdoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average. TVOC Concentrations

TVOCs were not detected anywhere in.side the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • ' The school building was occupied at the time of the assessment. • No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debris. FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of COg, CO and TVOCs were below the applicable standards and guidelines. 2. All of the indoor measurements for temperature were above the range of 68 to 75 °F (at 50 . percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. All of the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter . Fifty- seven (57) of the indoor measurements were above the USEPA recommended concentration . of 40 pg/m3 for sensitive individuals and children. All of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely, A TC ASSOCIA TES INC. Reviewed by:

Yiannis EfstathioiT James R. Cohn, CIH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC100_003271760

NYC-WTC_000328283

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000328283Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ memo, PS 89M, May 2002

NYC-WTC_000328340

ATC provides IAQ measurements for PS 89M; BOE requested air quality evaluation.

Similar indexed content