NYC 9/11 Public Portal Document
Pass Analytical Senfices. Inc.
170DEIm Strast Suite 200
'aceAnalytIcar Minneapolis, MN 55414
Phone: 612.807.1700
www.pacBlabs.eom REPORT OF: CHEMICAL ANALYSES Fax: 612.607.6444
f PROJECT: PCDD/PCDFWfsiALYSES DATE: January 9, 2002
PAGE: 7 REPORT NO: 01-1052540
S
RESULTS
The results from the analyses are presented in the following:
Appendix A - Documentation
a Appendix B - PCDD/PCDF Analysis Results
-Y
DISCUSSION
The recoveries of the isotopically-labeled PCDD/PCDF internal standards in the sample extracts
’ ranged from 56-125% and indicate a level of efficiency through the extraction and enrichment
steps that is considered typical for this matrix. All of the internal standard recoveries for the field
samples were within the target limits for this method. Also, since the quantifications of the native
2,3,7,8-substituted isomers were based on isotope dilution, the data were automatically corrected
for variation in recovery and accurate values were obtained.
A laboratory method blank was prepared and analyzed with the sample batch as part of our routine
quality control procedures. The results, found at the beginning of Appendix B, show the blank to be
free of PCDDs and PCDFs. This suggests that the sample processing steps did not impact the
results of the analyses.
II A laboratory spike sample was also prepared with the. sample batch by extracting a clean wipe that
had been fortified with native standard materials. The results, found at the end of Appendix B,
! show that the spiked native compounds were recovered at 108-115%. This indicates a high
j degree of accuracy for these determinations.
I
REPORT OP LABORATORY ANALYSIS
This report shall not be reproduced, except in full,
without the written consent of Pace Analytical Services, Inc.
CITY_21MC100_012156671
NYC-WTC_000326595
OCR can misread numbers and units. Confirm readings against the page image before using them.