Mr. Bernard R. Of S2-33iyiys£cy-3i:7:'i\--^ 2002 y. Indoor Air Quality Assessment Pages Pi S. 89M i 3 ^^YnWroiectWjT-^^

Real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental nteasurements consisting of Seventy- four (74) from inside the school building and six (6) outdoors. All five floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 3^'.2:05P.M.C -'i

Temperature

Indoor dry bulb temperature measurements ranged from 62.0 °F to 72,5 °F. Seventeen (17) measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHR,4E Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 50.0 to 53 .9 °F.

Relative Humidity

The relative humidity indoors ranged from 37.0 percent to 66,7 percent. Three (3) measurements were above tire ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 56.7 to 66.4 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 488 ppm to 534 ppm. One (1) COy measurement was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COy concentrations ranged from 488 to 534 ppm. Therefore, the maximum acceptable level of COg at this location was 1234 ppm (background level + 700 ppm). The highest CO2 reading was found in room 402. At the time of ATC’s assessment, this room was occupied by approximately thirty (30) people. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The school building during ATC’s assessment was not 3: occupied., .. £/ ,. 3 3,

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-lppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0-1 ppm-

Respirable Particulates (RMy,

Respirable particulate concentrations* indoors ranged between 21 pg/m? to 63 pg/rn^. All measurements were below the NPAAQS of 65 uuirC 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PMg.5 concentration for The entire school building was approximately 42 pg/m^. This average ;

CITY_21MC1OO_OO327O134

NYC-WTC_000326025

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000326025Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, P.S.89M, 2002

NYC-WTC_000327378

Indoor air quality measurements collected February 8-11, 2002 for PS 89M.

Similar indexed content

Compare copies and versions →