Indoor air quality report, PS 89M, Jan 2002

Machine-extracted title · confidence 28%

IAQ measurements collected at PS 89M, January 2002.

NYC-WTC_000326016–000326019
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan In d o or A ir Qu al ity As s e s sment /■;;;i:212;2/ 2 ;;2:2-^ Page^A P. S. 89 (Manhattan); ATC ProiecCNo. 15-19125-0297 recommended concentration of 40 pg/m^ for sensitive individuals / children. The average PMg ,5 concentration for the entire school building was approximately 11 pg/m^ . The outdoor respirable particulate concentration ranged from 12 - 20 pg/m^ with an average of 16 pg/m^ .

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average. ? /2 < 2 •

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVQG concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATG noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment: • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. CouCeiitrations of respirable particulates, CO2- CD and TVOCs were within applicable standardsand guidelines; C 2. Twenty (20) indoor measurements of relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. All other measurements were below the recommended range. 2^ 3. Two: (2) temperature measurements were above the range of 68 to 75° F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).

It is our pleasure to provide these indoor air quality services to the New York City Board of Educatioh. If you have any questions about this report, please call (212) 353-8280, extension 261 ur212. I" I Sincerely, 2 ATCASSOCIATES INC. Reviewed by:

Andreas G. Andreou James R. Cohn, GiHTCSP Senior Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_003270122

NYC-WTC_000326019

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000326019Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, P.S.89M, 2002

NYC-WTC_000327378

Indoor air quality measurements collected February 8-11, 2002 for PS 89M.

Similar indexed content

Compare copies and versions →