Mr. Bernard R. Orlan ■• I 1 January 19, 2002 I ndoor Air Quality Assessment Page 2 P. S. 89 (Manhattan) ATC Project No. 15-19125-0297
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all SLich assessments, there were inherent limitations created by constraints of ti me, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and rnay not represent conditions found at other times. The information presented in this report should be used by the BQE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications;
Ventilation fa?' Acceptable Indoor Air Quality (ASHRAE 62-/999}, American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions /or Human Occupancy (A.SHRAE 5S-1992/ Industrial Hygienists Guide to Indoor Air Quality Investigations {1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, sonie, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times. I
7. ■ HABLEl 7 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED ■TARGET I KVEI. ■ a(;encv or HMM lllli _____________ ORGWIZAIIOS BMinmi Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CQ2) ' above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from USEPA NPA AQS) Respirable 65 micrograms per cubic meter USEPA NpAAQS •7 , 2, Particulates (PM2,5) of air (tig/m3 ) 24-hour average Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter; 68-75°F at 50% RH ; Relative Humidity 30 - 60 % ASHRAE 55 - Total Volatile Organic CompOLinds I ppm AIHA (TVpCJ vTA. ■ USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_003270086
NYC-WTC_000325994
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000326002
IAQ measurements at PS 89M, January 2002, ATC Associates.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384011
ATC IAQ measurements collected January 21, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400563
IAQ report for January 18, 2002, at PS 89M with multiple measurements.
14 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245303
IAQ measurements at P.S. 89M; January 18, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245296
IAQ measurements at P.S. 89M; January 16, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000226873
ATC Associates report on indoor air quality measurements collected at P.S. 89M on January 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245321
ATC Associates reports IAQ measurements at P.S. 89M for NYC BOE, January 2002.
14 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383986
ATC IAQ measurements collected January 16, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245331
ATC Associates provides IAQ measurement results for P.S. 89M requested by NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400572
IAQ report for January 21, 2002 at P.S. 89M with measurement results.
14 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245312
Indoor air quality measurements at P.S. 89M; January 19, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236958
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000327350
ATC IAQ report for the NYC Board of Education; measurements to assess air quality before occupancy.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384011
ATC IAQ measurements collected January 21, 2002 at the referenced school.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400563
IAQ report for January 18, 2002, at PS 89M with multiple measurements.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000326002
IAQ measurements at PS 89M, January 2002, ATC Associates.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245312
Indoor air quality measurements at P.S. 89M; January 19, 2002.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245331
ATC Associates provides IAQ measurement results for P.S. 89M requested by NYC BOE.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000326002
IAQ measurements at PS 89M, January 2002, ATC Associates.
Similar indexed content
NYC-WTC_000384011
ATC IAQ measurements collected January 21, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000236958
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
Similar indexed content
NYC-WTC_000400563
IAQ report for January 18, 2002, at PS 89M with multiple measurements.
Similar indexed content
NYC-WTC_000245303
IAQ measurements at P.S. 89M; January 18, 2002.
Similar indexed content