ATC Environmental, Inc. 104 East 25th Street New York, New York 10010

N.Y.C. Board of Education Approved N.Y. State ELA? #10879 28-11 Queens Plaza North ACCREDITED NVLAP Lab Code # 1187 Long Island City, NY 11101 Report Date: 10/05/01

ASBESTOS FIBER ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM) With Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS) Method: AHERA Final Rule, EPA Federal Register {40 CFR, Part 763), Vol. 52, No. 210, October 30, 1987

Sarnole IdentificaCion Analysis Parameters

Project/Site: H.S. for Economics & Finance, IQO Trinity PI., NYC TSM Sample No.: 5606 60096 Entire Building Date Received: 10/04/01 Grid Openings Analyzed:__ 4

Project Sample No.: HSSF-5'lQ/3-0S Average Grid Opening: 106.00 um

Air Volume: 182Q liters Total Area Analyzed: 0.0450 mm2

Filter Tyoe: MCE 25 mm diatn., Pore Size: 0.45 um A.Talytical Sensitivity: 22.2 s/mni2 Effective Area: 385 mm2 0.0047 s/cc

FIBROUS PARTICULATES ANALYZED Number Observed CONCENTRATION Total Single Matrix Total. Struct. Filter Air Fibers "Bundles Clusters Struct. Struct > = Sum Struct/mm2 Struct/cc nam/m3

Chrysotile Asbestos 0 0 0 0 0 0 0.0 C.OOOO 0

JVnphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0

Ambiguous 0 0 0 0 0 0 0.0 0.0000 0

Total asbestos (includes ambiguous structures) 0 0 0.0 0 . 0000 □ Non-Asbestos 0 0 0 0 0 0 0.0 3 . 0000 N/A No Identification 0 0 0 0 0 0 C.0 0.0000 N/A

Totals (All Structures) 0 0 0.0 0.0000 N/A The estimated uncertainty of this analysis is 1 standard deviation.

Non-asbestos fiber i.d. (EDS/SAED) : None detected Amphibole Asbestos Type; None detected

The Analysis was carried out in accordance with the approved TEM method. This laboratory is in compliance with the quality specified for the method.

Analyzed by; Report Reviewed by:

Marek Peysakhov Michael A. Gorycki, Ph.D. Director of Electron Microscopy

CITY_21MC1OO_OO3267853 N YC-WT C_000324270

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000324270Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →