■Mr. Bernard P. Orlan November 20, 2001 Indoor .Air Quality Assessment Page 2 Murrav Beretraum Hieh School CMSPOl ATC Proiect No. 15-19125-0286
The assessment was perfonned consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE a.s a guide to assess the need for further improvements in cuinent indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society' of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environinenlal Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLEI TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGET LEVEL AGENCY OR ORGANIZATION Carbon Dioxide <700 pans per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHR.AE 62 (adopted from (CO) USEPA NPAAQS) ________ Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average Temperature Summer: 73-79°F at 50% RH ASHRAE55 Winter: 68-75°F at 50% RH Relative Humidity 30 -60 % ASHRAE 55 Total Volatile 1 ppm Organic Compounds AIHA (TVOC) USEPA = United States Environmental Protection Agency NPA.AQS = National Primary' Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC1OO_OO32669O3
NYC-WTC_000323940
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000323919
ATC Associates indoor air quality assessment at a NYC school in mid-November 2001.
12 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323925
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291841
Indoor air quality measurements report for 90 Trinity Place, May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323908
ATC Associates indoor air quality assessment at a New York City school on Nov 15, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330334
IAQ assessment report for HS project; includes interpretation by ATC.
13 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000324057
IAQ assessment report for PS 130M, Oct 16, 2001, by ATC Associates.
11 shared non-person entities · 1 shared topics · similarity 0.985
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000329843
IAQ assessment report for PS 130M school building.
11 shared non-person entities · 1 shared topics · similarity 0.985
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396309
ATC IAQ assessment at PS 234M, BOE, December 2001.
11 shared non-person entities · 1 shared topics · similarity 0.984
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236977
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236967
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236945
Report of indoor air quality measurements collected on January 24, 2002, at P.S. 89M.
13 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236953
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000311979
Nov 7, 2001 memo documenting IAQ assessment at Stuyvesant High School.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375541
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374808
IAQ measurements at PS 150M to evaluate air quality prior to re-occupancy, May 20, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311748
IAQ assessment report for Stuyvesant High School dated October 15, 2001.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404383
Report of indoor air quality measurements at PS 89M.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253571
ATC IAQ measurements at P.S. 150M for pre-occupancy evaluation by BOE.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000323919
ATC Associates indoor air quality assessment at a NYC school in mid-November 2001.
Similar indexed content
NYC-WTC_000323925
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
Similar indexed content
NYC-WTC_000291841
Indoor air quality measurements report for 90 Trinity Place, May 2002.
Similar indexed content
NYC-WTC_000323908
ATC Associates indoor air quality assessment at a New York City school on Nov 15, 2001.
Similar indexed content
NYC-WTC_000236977
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
Similar indexed content