.Mr. Bernard I’. Oriaii November I 5. 2001 ■ Indoor Air (Jnaliix .Assessment Page 3 SiLiwesant I licit School ( M477i .ATCProjeei_NtL_ 1^-19125-()24()
Real-Time iko^mem al Measurements
A fC collected sixty (60) sets of real-time environmental measurements consisting of (59) in the school building and one (I) outdoors. All seven Hoors of the school were surveyed. These results are described below. Field data sheets are found in Attachment I. Readings began at 12:00 P.M. and concluded after 3:00 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 73.1 °F to 77.6 °F. Forty-four (44) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASI IRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature was 67.5 °F.
Relative Humidiiv
The relative humidity indoors ranged from 30.3 percent to 37.6 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity was 39.9 percent.
Carhem Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 534 ppm to 980 ppm. All COn measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentration was 486 ppm. Therefore, the maximum acceptable level of COp at this location was 1186 ppm (background level -I- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COp indoors is occupant respiration.
C 'cirhon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. l lie outdoor CO concentration was 1-2 ppm.
Respirable Particii/atex (PMp^j)
Respirable particulate concentrations* indoors ranged between 42 jug/mJ to 100 gg/m^ with an average of approximately 83 gg/m-*. Only five (5) measurements were below the NPAAQS of 65 gg/m^ 24-hoiir average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 103 gg/m^.
* The measurements made during this assessment were instantaneous readings, the guidelines are adopted from 24-hour and annual averages.
CITY_21MC100_003266812
NYC-WTC_000323910
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000323925
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323919
ATC Associates indoor air quality assessment at a NYC school in mid-November 2001.
12 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323939
ATC Associates IAQ assessment report for the school in New York City.
14 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323914
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291841
Indoor air quality measurements report for 90 Trinity Place, May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.986
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312094
ATC memo accompanying IAQ report for Stuyvesant High School, dated November 16, 2001.
12 shared non-person entities · 1 shared topics · similarity 0.985
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000324057
IAQ assessment report for PS 130M, Oct 16, 2001, by ATC Associates.
11 shared non-person entities · 1 shared topics · similarity 0.984
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311704
Indoor air quality assessment conducted on October 10, 2001 at Stuyvesant High School.
12 shared non-person entities · 1 shared topics · similarity 0.984
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236967
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236977
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236953
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236945
Report of indoor air quality measurements collected on January 24, 2002, at P.S. 89M.
13 shared non-person entities · 1 shared topics · similarity 0.986
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000372105
ATC reports IAQ measurements at PS 234M, June 2002, for BOE to assess indoor air quality.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000272269
IAQ measurements collected at P.S. 234M for BOE program.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000272168
Indoor air quality measurements report for PS 234M, Feb 4, 2002.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314904
ATC IAQ report for P.S. 234M detailing measurements and BOE request.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000294458
Indoor air quality measurements at PS 234M, prepared for NYC BOE, March 2002.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315361
ATC indoor air quality measurements report for P.S. 234M delivered to BOE.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000323925
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
Similar indexed content
NYC-WTC_000323919
ATC Associates indoor air quality assessment at a NYC school in mid-November 2001.
Similar indexed content
NYC-WTC_000323939
ATC Associates IAQ assessment report for the school in New York City.
Similar indexed content
NYC-WTC_000323914
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
Similar indexed content
NYC-WTC_000236967
Letter from ATC Associates to NYC Board of Education reporting indoor air quality measurements at P.S. 89M collected on January 18, 2002.
Similar indexed content