NYC 9/11 Public Portal Document
ATC ASSOCIATES, INC
104 E 25th Street, 10th Floor
New York, NY 10010
Tel. 212-353-8280
Fax 212-353-8306
REPORT DATE: 08-07-02
1
CLIENT: Taylor Environmental Group, Inc.
PROJECT NAME: SCA/Stuyvesant HS
345 Chambers Street, NY
PROJECT NUMBER: M477-15217/29881
SAMPLED BY; Client
SAMPLE DATE: 08-05-02
1 DATE RECEIVED: 08-05-02
DATE ANALYZED: 08-05-02
SAMPLE MEDIA; Dust Wipe Sample
ANALYSIS REQUIRED: Method EPA 3050/7420
1'1
b
ANALYSIS RESULTS
SAMPLE BATCH SAMPLE DESCRIPTION LEAD DETECTION
ID NO. CONCENTRATION LIMIT
(Rg/ft*) (pg/ftR
11-01 20944 11th Floor HVAC #2 Louvre Supply <9.0 9.0
11-02 20944 11th Floor HVAC #1 Louvre Supply <9.0 9.0
05-03 20944 5th Floor Boys Locker Room HVAC #9 <9.0 9.0
n
05-04 20944 5th Floor Boys Locker Room HVAC #9 Supply <9.0 9.0
b
05-05 20944 5th Floor Corridor o/s 517 HVAC #1 Supply <9.0 9.0
05-06 20944 Sth Floor Cafeteria HVAC #10 Supply <9.0 9.0
FB-3 20944 Field Blank <9.0 pg 9.0 pg
FB-4 20944 Field Blank <9.0 pg 9.0 pg
NOTE 1:
ii THE REPORTING LIMIT (RL) IS 18.0 pg
NOTE 2:
HUD Guidelines for final clearance dust wipe samples: Floor 40 pg/ftL Window sills 250 pg/fF,
Window wells 400 pg/ftL Exterior surfaces 800 pg/ft’.
B NOTE 3:
Blank units are in pg
I
CITY_21MC100_011273914
NYC-WTC_000323568