1
REPORT DATE: 07-25-02
^7
CLIENT: Taylor Environmental Group, Inc.
PROJECT NAME: SCA/Stuyvesant HS
345 Chambers Street, NY
PROJECT NUMBER: M477-15217/29881
~T3
SAMPLED BY: Client
SAMPLE DATE: 07-24-02
n DATE RECEIVED: 07-24-02
DATE ANALYZED: 07-24-02
SAMPLE MEDIA: Dust Wipe Sample
ANALYSIS REQUIRED: Method EPA 3050/7420
J
ANALYSIS RESULTS
SAMPLE BATCH SAMPLE DESCRIPTION LEAD. DETECTION
ID NO. CONCENTRATION LIMIT
(gg/fi^ (pg/fi^
10-01 20613 10 Floor O/S Rm 1010 HVAC 1 West Supply <9.0 9.0
10-02 20613 10 Floor O/ S Rm 1010 HVAC 1 East Supply 37.4 9.0
10-03 20613 10 Floor O/S Rm 1007 HVAC 1 East Supply <9.0 9.0
10-04 20613 10 Floor O/S Rm 1010 HVAC IRetum Plenum <4.5 4.5
10-05 20613 10 Floor O/S Rm 1010 HVAC IRetum Plenum 5.5 4.5
10-06 20613 10 Floor O/S Rm 1018 HVAC Return Duct 34.7 9.0
FB-1 20613 Field Blank <9.0 ug 9.0 ug
U
FB-2 20613 Field Blank <9.0 ug 9.0 ug
NOTEl:
THE REPORTING LIMIT (RL) IS 18.0 ug
NOTE 2:
HUD Guidelines for final clearance dust wipe samples: Floor 40 ug/ft'. Window sills 250 u&Tt\
Window wells 400 ug^lF, Exterior surfaces 800 ug/fP-
a NOTES:
Blank units are in Ug