NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 2 pages

Air monitoring report, 104 East 25th St, May 2002

Machine-extracted title · confidence 42%

Real-time respirable particulates air monitoring across NYC BOE sites, May 7, 2002.

NYC-WTC_000315911–000315912
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 8, 2002 Respirable Particulate Monitoring Page 2 Various Locations/Manhattan ATC Project No. 15-19125-0314

TARGET GUIDELINES FOR AIR QUALITY PARAMETERS EVALUATED* PARAMETER TARGET LEVEL AGENCY Respirable 65 micro grams per cubic Particulates meter of air (pg/m^) 24 hour USEPA NPAAQS (PM2.5) average Respirable USEPA recommendation Particulates 40 gg/m3 24 hour average for children/sensitive (PMa^d individuals USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard REAL-TIME SAMPLING RESULTS

Thirty-one (31) indoor and thirty-four (34) outdoor respirable particulates measurements* were collected from twenty-nine (29) school locations in Manhattan, ranging from West 11* Street to East 33'^^ Street. The measurements were made from 5:51 A.M. to 4:53 P.M. The lAQ field report forms are provided as the Attachment.

The outdoor PMa.s concentrations ranged from 30 pg/m^ to 72 pg/m^ with rm average of 48 pg/m^. The indoor concentrations ranged from 24 pg/m^ to 58 pg/m3 with an average of 34 pg/m^. Two (2) of the outdoor readings were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Eight (8) of the indoor and twenty-seven (27) of the outdoor readings were above the USEPA recommended guideline for children and sensitive individuals of 40 pg/m^.

These measurements were instantaneous readings, the NPAAQS and the recommendation for children are 24-hour averages.

CONCLUSION Based on our measurements, two (2) of the outdoor readings were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Eight (8) of the indoor find twenty-seven (27) of the outdoor readings were above the USEPA recommended guideline for children and sensitive individuals of 40 pg/m^.

It is our pleasure to provide these air quality consultative services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 212 or 211.

Sincerely, ATC ASSOCIATES INC. Reviewed by:

Dannis Efstathiou James R. CohnT^IH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CrTY_21MC100_003048128 NYC-WTC_000315912

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000315912Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →