Mr. Bernard P. Orlan June 27,2002 Indoor Air Quality Assessment Page 4 P. S. 234M ATC Project No. 15-19125-0279

individuals and children. The outdoor respirable particulate concentration ranged from 326 |ig/m3 to 361 pg/m^ with an average of approximately 349 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

7'VOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The building was occupied at the time of the assessment; • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO, and TVOCs were within applicable standards and guidelines. 2. Seven (7) of the indoor measurements for temperature was below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. 3. One (1) of the indoor measurements was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading (1391 ppm) was recorded in Room 118 approximately at 11:00 AM. with 24 occupants. Levels above the recommended maximiun do not indicate a health risk. 4. Two (2) of the measurements collected indoors for respirable particulate concentrations were above the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Six (6) of the indoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280,ext # 290

Sincerely, ATC ASSOCIATES INC.

Prasad Doddapai^ni' Senior Project Manager

Attachment

CITY_21MC100_003032807

NYC-WTC_000315485

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000315485Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →