Mr. Bernard P. Orlan June 3,2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279

Temperature

Indoor dry bulb temperature measurements ranged from 68.7 °F to 77.9 °F. Eleven (11) of the indoor measurements for temperature were below and none of the measurements were above the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55- 1992 during the summer season. The outdoor temperature measurements was 68.7 °F for all readings.

Relative Humidity

The relative humidity indoors ranged from 43.6 percent to 64.9 percent. One (1) of the indoor measurements for relative humidity was above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity was 64.9 percent for all readings.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 571 ppm to 1126 ppm. All of the indoor measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 571 ppm. Therefore, the maximum acceptable level of CCY at this location was 1271 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COj indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors was 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 1 ppm for all readings.

Respirable Particulates (PM2,^

Respirable particulate concentrations* indoors ranged between 8 pg/m’ to 26 pg/m’ with an average approximately 13 pg/m^ None of the measurements collected indoors for respirable particulate concentrations were above the NPAAQS 65 pg/m’ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m’ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 19 pg/m’ to 20 pg/m’ with an average of approximately 24 pg/m\

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

CITY_21MC1OO_OO3O326O8

NYC-WTC_000315301

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000315301Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →