NYC-WTC_000315182
Indoor air quality measurements collected May 14, 2002 for PS 234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗ATC report of IAQ measurements for PS 234M requested by NYC BOE, May 20, 2002.
NYC-WTC_000315219–000315222OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 21,2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279
Real-Time Environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50) from inside the school building and ten (10) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 7:20 A.M. and concluded after 12:40 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.3 °F to 78.6°F. Fourteen (14) indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 60.8 to 61.1 °F.
Relative Humidity
The relative humidity indoors ranged from 21.4 percent to 28.9 percent. All indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 23.2 to 23.4 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 446 ppm to 1227 ppm. All of the measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 601 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1301 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 2 ppm for all collected readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 2 ppm for all readings.
Respirable Particulates (PM2,j)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 15 pg/m^ with an average approximately 11 pg/m-- None of the measurements collected indoors for respirable particulate concentrations were above the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 11 pg/m^ to 19 pg/m3 with an average of approximately 17 pg/m^.
CITY_21MC100_003032520
NYC-WTC_000315221
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000315182
Indoor air quality measurements collected May 14, 2002 for PS 234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397499
ATC provides IAQ measurements collected May 20, 2002 for PS234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315208
Indoor air quality measurements collected May 17, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397509
ATC IAQ measurements collected May 21, 2002 at PS234M for BOE review.
12 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397465
ATC IAQ measurements at PS234M, May 14, 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315149
ATC IAQ measurements at PS 234M for BOE program, May 9, 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315230
ATC IAQ measurements at PS 234M; BOE program to assess indoor air quality, May 21, 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315134
ATC IAQ measurements at PS 234M for BOE program, May 7, 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397489
ATC provides IAQ measurements for P.S. 234M in May 2002 per BOE request.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397455
ATC IAQ measurements at PS234M, May 13–15, 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315112
ATC IAQ measurements at PS 234M for BOE QA program, May 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315270
ATC report of indoor air quality measurements at PS 234M; BOE program, May 29, 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000315372
ATC IAQ measurements report for P.S. 234M prepared for BOE.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315241
ATC indoor air quality measurements at PS 234M for BOE program, May 22, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199225
ATC Associates reports indoor air quality measurements collected at P.S. 234M on June 13, 2002 for the NYC Board of Education.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397509
ATC IAQ measurements collected May 21, 2002 at PS234M for BOE review.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315149
ATC IAQ measurements at PS 234M for BOE program, May 9, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397465
ATC IAQ measurements at PS234M, May 14, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000315182
Indoor air quality measurements collected May 14, 2002 for PS 234M.
Similar indexed content
NYC-WTC_000397499
ATC provides IAQ measurements collected May 20, 2002 for PS234M.
Similar indexed content
NYC-WTC_000315208
Indoor air quality measurements collected May 17, 2002 at PS 234M.
Similar indexed content
NYC-WTC_000397509
ATC IAQ measurements collected May 21, 2002 at PS234M for BOE review.
Similar indexed content
NYC-WTC_000397465
ATC IAQ measurements at PS234M, May 14, 2002.
Similar indexed content