Mr. Bernard P. Orlan April 9, 2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279
Real-Time Environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50) from inside the school building and ten (10) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded after 1:50 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 70.1 °F to 72.0 °F. All indoor measurements for temperature were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions)^The outdoor temperature measurements ranged from 57.1 to 57.5 °F.
RelgtryeHumidify
The relative humidity indoors ranged from 29.1 percent to 32.9 percent. Ten (10) indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 32.4 to 32.7 percent.
CarbpnDioxideCpncenirqtipn
Carbon dioxide concentrations indoors ranged from 531 ppm to 637 ppm. All of the measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 611 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1311 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 0 ppm for all readings.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 14 pg/m^. None of the indoor or outdoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Also none of the measurements were above the USEPA recommended concentration of 40 pg/m3 for sensitive individuals and children.
CITY_21MC100_003032188
NYC-WTC_000314946
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000314954
Air quality measurements collected at P.S. 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397287
ATC report of IAQ measurements conducted on Apr 15, 2002 at PS 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314964
Indoor air quality measurements collected at P.S. 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397241
Indoor air quality measurements report for P.S. 234M, Apr 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397251
IAQ measurements report for P.S. 234M, Apr 2002; scope of work described.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397261
IAQ measurements report for PS 234M; April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000294458
Indoor air quality measurements at PS 234M, prepared for NYC BOE, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000294482
Indoor air quality measurements collected March 26, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314985
Indoor air quality measurements collected at P.S. 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000381436
Indoor air quality measurements at PS 234M; March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314815
IAQ measurements collected March 19, 2002 at PS 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314825
IAQ measurements collected March 18, 2002 at PS 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000397261
IAQ measurements report for PS 234M; April 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397251
IAQ measurements report for P.S. 234M, Apr 2002; scope of work described.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397241
Indoor air quality measurements report for P.S. 234M, Apr 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314964
Indoor air quality measurements collected at P.S. 234M for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371824
ATC IAQ measurements report prepared for BOE at PS 234M in April 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000294472
Indoor air quality measurements at PS 234M, documenting March 22, 2002 activities.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000314954
Air quality measurements collected at P.S. 234M for BOE.
Similar indexed content
NYC-WTC_000397287
ATC report of IAQ measurements conducted on Apr 15, 2002 at PS 234M for BOE.
Similar indexed content
NYC-WTC_000314964
Indoor air quality measurements collected at P.S. 234M for BOE.
Similar indexed content
NYC-WTC_000397241
Indoor air quality measurements report for P.S. 234M, Apr 2002.
Similar indexed content
NYC-WTC_000397251
IAQ measurements report for P.S. 234M, Apr 2002; scope of work described.
Similar indexed content