IAQ report, P.S. 234M, Feb 28 2002

Machine-extracted title · confidence 40%

Indoors air quality measurements at P.S. 234M per BOE request.

NYC-WTC_000314934–000314937
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 1,2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279

Real-Time Environmental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded after 1:45 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 70.8 °F to 78.7 °F. Fifteen (15) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 36.3 to 37.9 °F.

Relative Humidity

The relative humidity indoors ranged from 9.8 percent to 25.5 percent. All of the indoor of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 30.1 to 33 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 594 ppm to 2081 ppm. Twenty-three (23) of the measurements were above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 488 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1188 ppm (background level 4- 700 ppm). One of the twenty-three (23) high readings was above 2000 ppm. The highest measurement was recorded in Room 315. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 0 ppm.

Respirable Particulates (PM2,3)

Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 20 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 14 pg/m^. This average concentration was below the USEPA recommended concentration for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentration ranged from 13 to 30 pg/m^ with an average of 23 pg/m3.

ClTY_21MC100_003032111

NYC-WTC_000314936

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000314936Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →