Mr. Bernard P. Orlan February 28, 2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279

Real-Time Environmental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded after 1:45 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 65.0 °F to 75.6 °F. Four (4) measurements were above and eight (8) were below the range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 45.4 to 46.3 °F.

Relative Humidity

The relative humidity indoors ranged from 24.4 percent to 41.9 percent. Thirteen (13) of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative, humidity ranged from 31.3 to 34.0 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 618 ppm to 3439 ppm. Thirty-one (31) of the measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 477 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1177 ppm (background level + 700 ppm). Eight of the thirty-one (31) high readings were above 2000 ppm and one (1) of those was over 3000 ppm. All eight readings were collected from the third floor. The highest measurement was recorded in room 305. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 0 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 12 pg/m^ to 24 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 17 pg/m^. This average concentration was below the USEPA recommended concentration for sensitive individuals such

CITY_21MC100_003031805

NYC-WTC_000314648

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000314648Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →