Mr. Bernard P. Orlan May 7, 2002
Indoor Air Quality Assessment Page 4
P. S. 89M ArCPrqiectNqJ5-19125-0297
respirable particulate concentration measurements ranged from 88 to 96 pg/m^ with an average
of 92 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Qmcentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The school building was occupied at the time of the assessment.
• No smoke odor was detected in the building
• The interior of the building appeared clean and free of dust and debris.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO2, CO and TVOCs were below applicable standards and guidelines.
2. Twenty -three(23) of the indoor measurements for temperature were below the range of 73 to
79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992
during the summer
3. All indoor measurements for relative humidity were within the ASHRAE-recommended
range of 30 to 60 percent for occupant comfort.
4. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average
concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the
USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or 290.
Sincerely,
A TC ASSOCIA TES INC.
Reviewed by:
James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager, Industrial Hygiene Division