Mr. Bernard P. Orlan April 26, 2002 Indoor Air Quality Assessment Page 3 P^:S9M__________________________________ ATC Project No. 15-19125-0297 Reai -Timi. Exairoxmkm ai Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11:30 A.M.
Temperature
Indoor dry bulb temperature measurement.s ranged from 64.3 °F to 76.1 °F. Sixty-ninc (69) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAF Standard 55-1992 during the summer season . The outdoor temperature measurements ranged from 53.1°F to 53.5°F.
Relative Humidity
'fhe relative humidity indoors ranged from 34.1 to 38.7 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 33.6 to 33.9 percent.
C^rbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 510 ppm to 1112 ppm. All of the indoor measurements for CO2 were below the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 461 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1161 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. ITie school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors was 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration wa.s also 1 ppm for all collected readings.
Respirable Particulates (PM2^5)
Respirable particulate concentrations* indoors ranged between 13 pg/m^ to 21 ug/m^. The average PM2.5 concentration for the entire school building was approximately 17 g/m^. All of the indoor and outdoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 21 to 23 pg/m^ with an average of 22 pg/m^.
CITY_21MC100_003047625
NYC-WTC_000313542
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000313528
ATC IAQ measurements at PS 89M for school building evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313837
ATC indoor air quality measurements conducted June 10, 2002 for PS 89M per BOE request.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369254
IAQ parameters with temperature, humidity, and gas readings.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394477
IAQ measurements collected April 25, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394514
IAQ measurements collected April 30, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394489
Indoor air quality report for PS 89M with April 26, 2002 measurements.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000211016
Report of indoor air quality measurements conducted at P.S. 89M on June 10, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313568
Indoor air quality measurements collected at PS 89M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369126
May 2002 IAQ measurements at P.S. 89M for BOE evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328314
Indoor air quality measurements collected on April 26, 2002 for the school.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392864
ATC report of IAQ measurements at PS 89M requested by BOE.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394465
April 2002 IAQ report for P.S. 89M, with BOE-referenced measurements.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000220668
Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 25, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000211000
Report of indoor air quality measurements conducted at P.S. 89M on May 29, 2002.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313774
ATC report of indoor air quality measurements for PS/89M.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374988
ATC IAQ measurements collected June 26, 2002 at P.S. 150M for pre-occupancy check.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369126
May 2002 IAQ measurements at P.S. 89M for BOE evaluation.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392706
ATC indoor air quality measurements conducted at P.S. 89M for BOE evaluation.
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000313528
ATC IAQ measurements at PS 89M for school building evaluation.
Similar indexed content
NYC-WTC_000313837
ATC indoor air quality measurements conducted June 10, 2002 for PS 89M per BOE request.
Similar indexed content
NYC-WTC_000369254
IAQ parameters with temperature, humidity, and gas readings.
Similar indexed content
NYC-WTC_000394477
IAQ measurements collected April 25, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000394514
IAQ measurements collected April 30, 2002 at the referenced school.
Similar indexed content