IAQ report, PS 89M, Apr 26, 2002

Machine-extracted title · confidence 40%

Indoor air quality measurements collected at PS 89M for BOE.

NYC-WTC_000313540–000313543
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 26, 2002 Indoor Air Quality Assessment Page 3 P^:S9M__________________________________ ATC Project No. 15-19125-0297 Reai -Timi. Exairoxmkm ai Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11:30 A.M.

Temperature

Indoor dry bulb temperature measurement.s ranged from 64.3 °F to 76.1 °F. Sixty-ninc (69) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAF Standard 55-1992 during the summer season . The outdoor temperature measurements ranged from 53.1°F to 53.5°F.

Relative Humidity

'fhe relative humidity indoors ranged from 34.1 to 38.7 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 33.6 to 33.9 percent.

C^rbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 510 ppm to 1112 ppm. All of the indoor measurements for CO2 were below the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 461 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1161 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. ITie school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors was 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration wa.s also 1 ppm for all collected readings.

Respirable Particulates (PM2^5)

Respirable particulate concentrations* indoors ranged between 13 pg/m^ to 21 ug/m^. The average PM2.5 concentration for the entire school building was approximately 17 g/m^. All of the indoor and outdoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 21 to 23 pg/m^ with an average of 22 pg/m^.

CITY_21MC100_003047625

NYC-WTC_000313542

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000313542Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

IAQ report for PS 89M, Apr 2002 · page 3

NYC-WTC_000220668

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 25, 2002.

Similarity score 0.994 (not a probability)

machine-extracted · confidence unavailable · Check page ↗

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, PS 89M, COE

NYC-WTC_000313837

ATC indoor air quality measurements conducted June 10, 2002 for PS 89M per BOE request.

Similar indexed content

Compare copies and versions →