NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 5 pages

Indoor air quality report, PS 89M, Apr 2002

Machine-extracted title · confidence 48%

ATC IAQ measurements at PS 89M for BOE air quality evaluation.

NYC-WTC_000313487–000313491
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 18,2002 Indoor Air Quality Assessment Page 4 P. S. 89M ATC Project No. 15-19125-0297 recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 10.5 to 122 pg/m^ with an average of 110 pg/m^. All of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentrations

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following; • The school building was occupied at the time of the assessment. • No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debris.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO;;, CO and TVOCs were below the applicable standards and guidelines. 2. Sixty (60) of the indoor measurements for temperature were above and ten (10) were within the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3„ All of the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. The average PM2.5 concentration for the entire school building was approximately 74 g/m^. Foily-nine (49) of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Seventy-five (75) of the eight (80) indoor instantaneous measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. All of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

CITY_21MC100_006739432

NYC-WTC_000313490

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000313490Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

IAQ report for PS 89M, Apr 2002 · Box unavailable

NYC-WTC_000220651

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 17, 2002.

14 shared non-person entities · 1 shared topics · similarity 0.999

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

IAQ report for PS 89M, Apr 2002 · page 4

NYC-WTC_000220651

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 17, 2002.

Similarity score 0.999 (not a probability)

machine-extracted · confidence unavailable · Check page ↗

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report for PS 89M, Apr 2002

NYC-WTC_000220651

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 17, 2002.

Similar indexed content

Compare copies and versions →