Mr. Bernard P. Orlan February 27, 2002 Indoor Air Quality Measurements Page 2 Stuyvesant High School (M477) ATC Project No. 15-19125-0246 The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice vaiiability, variations in indoor air quality parameters and sampling and analytical accuracy.
The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in cuirent indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publicaiions:
Ventilation for Acceptable Indoo7' Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Uonditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
Hi __________ Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from ^CO)______________ USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (gg/m^) 24-hour average 40 gg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_003045450
NYC-WTC_000311666
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000402177
March 11, 2002 IAQ measurements report for Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270030
ATC IAQ measurements conducted March 18, 2002 at Stuyvesant High School for NYC BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311646
Indoor air quality measurements collected on February 25, 2002 for Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402099
ATC IAQ measurements conducted on Feb 28, 2002 for Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270018
ATC IAQ measurements conducted March 13, 2002 at Stuyvesant High School for NYC BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402065
February 2002 ATC report on indoor air quality measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402206
ATC IAQ measurements report for Stuyvesant High School, March 15, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336458
Indoor air quality measurements collected March 18, 2002 at Stuyvesant HS.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402082
February 2002 ATC memo regarding IAQ measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336433
Indoor air quality measurements collected for Stuyvesant High School by ATC.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372779
Indoor air quality measurements collected at Stuyvesant High School, April 24, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336492
Indoor air quality measurements collected March 26, 2002 for BOE at Stuyvesant HS.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000336335
ATC IAQ report for Stuyvesant High School dated Mar 4, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402206
ATC IAQ measurements report for Stuyvesant High School, March 15, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336377
IAQ measurements collected at Stuyvesant High School; March 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402177
March 11, 2002 IAQ measurements report for Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336411
ATC IAQ report for Stuyvesant HS; measurements collected March 11, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256198
IAQ measurements collected for Stuyvesant High School in Feb–Mar 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
March 11, 2002 IAQ measurements report for Stuyvesant High School.
Similar indexed content
NYC-WTC_000270030
ATC IAQ measurements conducted March 18, 2002 at Stuyvesant High School for NYC BOE.
Similar indexed content
NYC-WTC_000311646
Indoor air quality measurements collected on February 25, 2002 for Stuyvesant High School.
Similar indexed content
ATC IAQ measurements conducted on Feb 28, 2002 for Stuyvesant High School.
Similar indexed content
NYC-WTC_000270018
ATC IAQ measurements conducted March 13, 2002 at Stuyvesant High School for NYC BOE.
Similar indexed content