Mr. Bernard P. Orlan February 8, 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School fM477) ATC Project No. 15-19125-0246

Real-Time Environmental Measurements

ATC collected one hundred and twenty-one (121) sets of real-time environmental measurements consisting of one hundred and nineteen (119) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 1:25 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 69.3°F to 73.6°F. All of the measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 46.5 to 57.1 °F.

Relative Humidity

The relative humidity indoors ranged from 24.1 percent to 27.6 percent. All of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity levels were 43.1 and 45.8 percent.

Carbon Dioxide Concentratim

Carbon dioxide concentrations indoors ranged from 510 ppm to 1151 ppm. All of the CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. Tlie outdoor (background) CO2 concentrations were 529 and 531 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1231 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 0 to 1 ppm.

Respirable Particulates (PM2_5)

Respirable particulate concentrations* indoors ranged between 13 ug/m^ to 21 pg/m^ with an average of approximately 17 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommendation of 40 pg/m3 for sensitive individuals and children. The outdoor respirable particulate concentrations were 41 and 56 pg/mA

In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5

CITY_21MC100_003045318

NYC-WTC_000311538

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311538Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, February 2002

NYC-WTC_000197500

Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in February 2002.

Similar indexed content

NYC-WTC_000311502

ATC IAQ measurements report for Stuyvesant High School, Feb 2002.

Similar indexed content

NYC-WTC_000311608

ATC IAQ measurements report for Stuyvesant High School dated February 14, 2002.

Similar indexed content

Compare copies and versions →