NYC 9/11 Public Portal Document

Potable Water Sampling H.S. of Economics & Finance (M833) June 20, 2002

DATE LO^’AT1O^ ASALVTK AI RFSl I TS III __ SAMPLED March 21, 2002 Kitchen /2"‘^ Floor Potability (Follow-up) Elevated levels of color and Hallway turbidity in 2"“^ Floor Hallway. June 18, 2002 2® Floor Hallway Potability (Follow-up) Elevated levels of color and turbidity in 2"*^ Floor Hallway. *House tank flushed prior to ATC investigation.

Please refer to Attachment A of this report for a detailed listing of sample locations and laboratory results for this investigation as well as results of samples collected during previous investigations conducted by ATC.

Conclusions and Recommendations

Follow-Up testing results indicated that flushing at the potable water outlet within the 2"*^ Floor Hallway outlet did not reduce the level of color or the level of turbidity below the NYSDOH MCL during the most recent round of testing. Repeated flushing of the house tank and outlets has not lowered the levels of color and turbidity to acceptable levels, in fact, the levels of both turbidity and color had actually increased from prior sampling conducted on March 21,2002.

Although flushing of the house tank and localized flushing at outlets in the school has been performed on several occasions and has lowered levels of color, iron and turbidity at most of the outlets, it is possible that the conditions that were present prior to initial sampling at the outlets may return. ATC recommends that an investigation of the system should be performed by certified personnel to determine the cause of these conditions and a recommendation should be provided as to how to reduce levels of color, iron and/or turbidity where necessary to meet the required guidelines.

ATC appreciates the opportunity to provide these services to the New York City Board of Education. If you should have any questions about the information presented in this report, please feel free to call me at 212-353-8280 ext.211.

Sincerely,

INC. /

AYiannis Efs Senior Project Manager

Attachment

CITY_21MC100_003028953

NYC-WTC_000310712

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000310712Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000374128

ATC follow-up potable water sampling at HS of Economics & Finance on June 18, 2002.

Similar indexed content

Compare copies and versions →