Mr. Bernard P. Orlan September 6, 2002 Indoor Air Quality Assessment , Page 2 P.S. 42M ATCProiectNo. 15-19125-0342
The results of the sampling represent conditions found on the date of the survey and may not represent conditions found at other times. The information presented in this report should be used by the DOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-2001), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), Amencan Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
gpMMTERgMj TARCET LEVEL ;: hi
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m3) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30-60% ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = Amencan Industrial Hygiene Association
CITY_21MC100_003042772
NYC-WTC_000309813
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000309803
ATC indoor air quality memo regarding PS 42M measurements.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000350145
ATC September 4-6, 2002 indoor air measurements at PS 42M for DOE.
10 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309794
DOE-requested indoor air quality measurements at PS 42M, Sept 2002.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000350068
Indoor air quality measurements at PS 42M; DOE requested assessment Sept 2002.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309350
Indoor air quality measurements at PS 2M, Aug 23, 2002.
10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309359
Memo regarding IAQ measurements at PS 2M, Aug 23, 2002.
9 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309368
Memo noting indoor air quality measurements at PS 2M, Aug 2002.
9 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239058
Letter from ATC Associates reporting indoor air quality measurements collected at P.S. 126M on August 28, 2002.
10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000351363
Memorandum noting IAQ measurements at PS 42M, DOE, Sep 2002.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000202383
ATC Associates report on indoor air quality measurements collected at the school on September 9, 2002.
10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000207776
Report on indoor air quality measurements collected at a Department of Education school to verify acceptable air conditions.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328671
August 2002 indoor air quality measurements at PS 2M for DOE.
10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000309368
Memo noting indoor air quality measurements at PS 2M, Aug 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309359
Memo regarding IAQ measurements at PS 2M, Aug 23, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000175150
Letter and report from ATC Associates regarding indoor air quality measurements collected at DeSoto School in August 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239058
Letter from ATC Associates reporting indoor air quality measurements collected at P.S. 126M on August 28, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000316199
ATC report of IAQ measurements at the referenced NYC DOE school, August 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309794
DOE-requested indoor air quality measurements at PS 42M, Sept 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000309803
ATC indoor air quality memo regarding PS 42M measurements.
Similar indexed content
NYC-WTC_000350145
ATC September 4-6, 2002 indoor air measurements at PS 42M for DOE.
Similar indexed content
NYC-WTC_000309794
DOE-requested indoor air quality measurements at PS 42M, Sept 2002.
Similar indexed content
NYC-WTC_000350068
Indoor air quality measurements at PS 42M; DOE requested assessment Sept 2002.
Similar indexed content
NYC-WTC_000309350
Indoor air quality measurements at PS 2M, Aug 23, 2002.
Similar indexed content