Mr. Bernard P. Orlan August 29, 2002 Indoor Air Quality Assessment Page 3 P.S. 1 M ATC Project No. 15-19125-0340
Real-Time Environmental Measurements
ATC collected fifty (50) sets of real-time environmental measurements consisting of forty-eight (48) in the school building and two (2) outdoors. All floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected during school hours. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 78.9 to 87.0 °F. Forty seven (47) of the indoor measurements were above the range of 73 to 79 °F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the summer season. The outdoor temperature measurements were 84.1 and 85.4 °F collected before and after the indoor samples.
Relative Humidity
The relative humidity indoors ranged from 37.5 percent to 55.4 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements were 50.6 and 51.6 percent collected before and after the indoor samples.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 481 ppm to 1086 ppm. All indoor measurement for CO2 were below the ASHRAE Standard 62-2001 recommended maximum concentration of <700 ppm above the background level. The average outdoor (background) CO2 concentration was 470 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1170 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 2 ppm to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The average outdoor CO concentrations was 2 ppm.
Respirable Particulates (PM2_s)
Respirable particulate concentrations* indoors ranged between 24 pg/m^ to 76 pg/m^. One of indoor measurement collected on the third floor for PM2.5 was above the NPAAQS of 65 pg/m^ 24-hour average concenfration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Fourteen (14) of the forty-eight (48) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.;.The-_two outdoor respirable particulate concentrations were 40 pg/m^ and 43 pg/m3 with an average of 41.5 pg/mA Both outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter but it was above the
CITY_21MC100_003042151
NYC-WTC_000309457
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000350024
Memo/letter from ATC regarding DOE project PS IM at 28-11 [name], Aug 2002.
12 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309465
ATC IAQ measurements report for Alfred E. [name] (P.S. IM), Aug 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000238526
Report detailing indoor air quality measurements collected at P.S. 2M for the New York City Department of Education.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000310159
ATC indoor air quality measurements at a DOE school for August 27, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000316583
ATC memo documenting IAQ measurements at the DOE site in Aug 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000316563
ATC notes on indoor air quality measurements taken at a NYC school.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000316573
ATC memo describing IAQ measurements conducted at the DOE facility.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328522
Indoor air quality IAQ report for Dr. [name] at J.H.S. 131M; August 22, 2002 measurements.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328765
Indoor air quality measurements at DeSoto School PS 130M.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199261
ATC Associates reports indoor air quality measurements collected at J.H.S. 131M on August 22, 2002 to verify acceptable air quality.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000316199
ATC report of IAQ measurements at the referenced NYC DOE school, August 2002.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000317091
IAQ memo documenting measurements at DeSoto School (PS 130M) in Aug 2002.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000350024
Memo/letter from ATC regarding DOE project PS IM at 28-11 [name], Aug 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309465
ATC IAQ measurements report for Alfred E. [name] (P.S. IM), Aug 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000309368
Memo noting indoor air quality measurements at PS 2M, Aug 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000207966
Report detailing indoor air quality measurements collected at a school location on August 23, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000316861
ATC Associates provided IAQ measurements taken at the referenced NYC Department of Education school on August 23, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000316573
ATC memo describing IAQ measurements conducted at the DOE facility.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000350024
Memo/letter from ATC regarding DOE project PS IM at 28-11 [name], Aug 2002.
Similar indexed content
NYC-WTC_000309465
ATC IAQ measurements report for Alfred E. [name] (P.S. IM), Aug 2002.
Similar indexed content
Report detailing indoor air quality measurements collected at P.S. 2M for the New York City Department of Education.
Similar indexed content
NYC-WTC_000310159
ATC indoor air quality measurements at a DOE school for August 27, 2002.
Similar indexed content
NYC-WTC_000316583
ATC memo documenting IAQ measurements at the DOE site in Aug 2002.
Similar indexed content