Respirable particulate IAQ report, M477 High School, Apr 2002

Machine-extracted title · confidence 42%

ATC report on six-date respirable particulate monitoring at the school building.

NYC-WTC_000308767–000308769
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 10,2002 Respirable Particulate Assessment Page 2 Stuwesant High School (M477') ATC Project No. 15-19125-0246

EVALUATION CRITERIA

Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. Table 1 lists target guideline for the parameter that ATC evaluated during this investigation. Meeting the listed value does not assure that acceptable indoor air quality will be achieved at all times.

TABLEI TARGET GUIDELINES FOR IAQ PARAMETER EVALUATED

65 micrograms per cubic Respirable meter of air (pg/m’’) 24-hour USEPA NPAAQS Particulates (PM2.5) average________________ 40 micrograms per cubic USEPA recommendation for meter of air (pg/m^) 24-hour children and sensitive average individuals USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard

RESULTS

ATC collected one (1) real-time 24-hour data-logging respirable particulate measurement and one 24-hour gravimetric sample in Main Lobby on each day. The two types of samplers were placed side-by-side at the sampling location. The results are shown in Table 2, TABLE 2 MAIN LOBBY 24-HOUR AVERAGE PM^ j CONCENTRATIONS BY SAMPLING DEVICE ug/m^)* * <I

March 11-12 7.0 16.0 March 13-14 10.0 9.72 March 15-16 210 20.1 March 19-20 "10' ■9^

March 20-21 <147 March 25-26 "To" 3.47 * micrograms per cubic meter of air The Dust Trak®data summaries and graphs are provided in Attachment 1, the laboratory results of the MEM® samples are provided in Attachment 2.

CITY_21MC100_003056655

NYC-WTC_000308768

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000308768Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000401078

ATC respirable particulate IAQ assessment report for Stuyvesant High School (M477), Apr 2002.

Similar indexed content

Compare copies and versions →