Mr. Bernard P. Orlan January 28, 2002
Wipe Sampling for PCBs Page 2
Stuyvesant High School (Manhattan) ATC Project No. 15-19125-0246
• 2nd floor bridge entrance hallway - wall;
• AC#2 mixed air plenum - floor (on January 18, 2002).
• AC#1 mixed air plenum - floor (on January 9, 2002).
Each sample was analyzed for seven PCB compounds with differing percentages of chlorine.
The PCB results of all samples rvere below the reporting limits (2.0 micrograms/sample). The
same level was reported in the blanks.
Currently, the Environmental Protection Agency spill clean-up standard for PCBs on non-porous
surfaces is 10 micrograms per 100 square centimeters or less (<10 ug lOOcmd) as stated in 40
CFR761.
It is our pleasure to provide these indoor environmental services to the New York City Board of
Education. If you have any.questions about this report, please call (212) 353-8280, extension
212 or 261.
Sincerely,
A TC ASSOCIA TES INC.
James R. Cohn, CIH, CSP
Regional Manager
Industrial Hygiene Division